Ultra1000 Series Toxic & Oxygen Deficiency

The Ultra1000 Series is a 24 VDC powered toxic gas detector consists of an interface module in a flame proof instrument enclosure and a 316 Stainless Steel sensor head assembly. The detectors monitors a variety of toxic gases in the parts per million (ppm) range, including: ammonia, carbon monoxide, chlorine, chlorine dioxide, hydrogen, hydrogen chloride, hydrogen sulfide, nitric oxide, nitrogen dioxide, oxygen deficiency, and sulfur dioxide.

The interface module is microprocessor-based electronic assembly with analog and digital circuitry to process the sensor signal for control, data display and to transmit the signal to a Gas Control Panel or to a PLC. In addition, Ultra1000 Series detector includes warning, alarm, and fault relay contacts that can be used to indicate an alarm or fault condition and Modbus communication

View Data Sheet   Technical Specifications

Applications

  • Drilling Rigs
  • Offshore Platforms
  • Petrochemical Industry
  • Chemical Storage
  • Water & Wastewater Treatment
  • LPG Storage
  • Refineries

Key Features

  • LCD display with back light
  • Simple one person auto Calibration
  • Three programmable alarm relays
  • Linear 4-20mA Output
  • RS-485 MODBUS RTU
  • Wide Power input range
  • Reverse Polarity protection
  • Provides complete status & control capability in the control room

Technical Specifications

Sensor Type

Electrochemical Cell

Measuring Range

Ammonia (NH3) 0-50 ppm
Carbon Monoxide (CO) 0-100, 0-1000 ppm
Chlorine (CL2) 0-10 ppm
Chlorine Dioxide (CLO2) 0-50 ppm
Ethylene (C2H4) 0-100 ppm
Ethylene Oxide (C2H4O) 0-50 ppm
Hydrogen Chloride (HCL) 0-20 ppm
Hydrogen Sulfide (H2S) 0-100, 0-500 ppm
Hydrogen (H2) 0-200ppm
Methyl Mercaptan (CH3SH) 0-100 ppm
Nitrogen Dioxide (NO2) 0-20 ppm
Nitric Oxide (NO) 0-100 ppm
Oxygen Deficiency (O2) 0-25 %(volume)
Sulfur Dioxide (SO2) 0-100 ppm

Accuracy

± 2 ppm or ± 10% of reading, whichever is greater.

Zero Drift

< 5% per year

Response Time

CO, H2, H2S, NO2 T90 < 30 s
NO, SO2 T90 < 15 s
NH3 T90 < 60 s
O2 T90 < 15 s

Electrical Classifications

Explosion Proof Enclosure

ATEX: II 2G Ex d IIC T6
CSA: Class I, Div 1 & 2, Groups B, C & D
C22.2 No 30-M1985 &
C22.2 No 142-M1987

Approvals

CSA, ATEX / IECEx, ABS Type Approved

Operating Temperature Range

H2S: -40°F to +149°F (-40°C to +65°C) (intermittent)

All others: -30°F to +122°F (-34°C to +50°C)

Humidity Range

15 - 90% RH (non condensing)

Storage Temperature

Electronics Interface Module:
  -40°F to +185°F (-40°C to +85°C)

Sensor Head Assembly:
  32°F to +68°F (0°C to +20°C) (cell)

Dimensions

Height: 7.4 inches (188 mm)
Width: 6.2 inches (159 mm)
Depth: 4.9 inches (125 mm)

Ingress Protection

NEMA 4X, IP66

Display and Indicators

2 x 8 character LCD display with back light

Power Input

12- 28 VDC (24 VDC Nominal)

Power Consumption

< 1 Watt

Alarm Relays

Programmable Low and High Alarms, Fault Alarm
  SPDT Form "C" Relay
  2 A @ 250 VAC or 30 VDC

Analog Output

Linear 4-20 mA output

  Fault: 0 mA
  Calibrate Mode: 2 mA
  Over Range: > 21 mA

Digital Output

Half Duplex RS-485
MODBUS RTU Protocol

Input / Output Protection

  • Transient over voltage suppressor
  • Reverse Polarity protection
  • EMI / RFI Immunity

Cable Requirement

Three wire shielded cable for power and analog signal.

Max of 300 Ω load for analog output

Accessories

Dust or Splash guard, Flow Adapter with tube fittings, Sensor Duct Mount Kit, Pole Mount brackets.

Cable Entry

3/4" NPT Female Adapter available for 1/2” NPT or M20

 